Chillers
LOGICOOL
Chillers
29
Technical Manual : 6521355 V1.8.0 07/2014
General Specification
MECHANICAL DATA
LCC20
LCC40
Capacity
Nom Output - Cooling - DX (Mechanical)
(1)
kW
18.2
33.7
Nom Input - Cooling DX (Mechanical)
(1)
kW
7.1
14.4
EER - DX (Mechanical)
(2)
2.56
2.34
ESEER
(3)
2.5
3.0
FSEER
(4)
3.4
4.2
Nom Cooling - Free Cooling
(5)
kW
12.0
21.0
Capacity Steps
%
0, 20 - 100
0, 10 - 100
Dimensions - H x W x L
mm
2060 x 1160 x 1290
2230 x 1370 x 1400
Weight
Machine
(6)
kg
530
620
Operating
(6)
kg
540
635
Construction
Base: Plain Galvanised Steel
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint
- Light Grey, (RAL 7035)
Material / Colour
Evaporator
Stainless Steel Brazed Plate
Insulation
Class 1 / UV Stable
Water Volume
l
1.5
3.0
Total Max. Water Flow
l/s
1.1
2.4
Condenser
Copper Tube/ Aluminium Fins
Face Area (Total)
1.23
1.75
Nominal Airflow
m³/s
3.30
4.40
Fan & Motor
Axial - Sickle Bladed Fan
Quantity
1
1
Diameter
mm
710
800
Maximum Speed
rpm
900
1100
Compressor
Single
Digital Scroll
Tandem
1 Digital + 1 Standard Scroll
Type
Quantity
1
2
Oil Charge Volume (Total)
l
1.69
1.69
Oil Type
Polyol Ester
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve (EEV)
Refrigerant Type - Precharged
R410A
Charge (Total)
kg
6.8
10.3
Connections
Water Inlet / Outlet - Type
PN16
PN16
Water Inlet / Outlet - Size
in
1 1/4
1 1/2
Water Drain/Bleed
in
1/2
1/2
Water System
Min. System Water Volume
(7)
l
112.0
207.4
Max. System Press
bar
10
10
OPTIONAL EXTRAS
Water Pump
(1)
In Line Pump
Max. System Press
bar
7
7
Nom. External Head:
Single / Run & Standby - Standard
kPa
85
87
Single / Run & Standby - Larger
kPa
169
162
Expansion Vessel
Water Capacity
l
8
12
(1)
Based on 12/7°C water temperature and 35°C ambient with a 20% Ethylene Glycol Water Concentration.
(2)
EER
=
Output kW
Where: Output kW = DX (Mechanical) Cooling duty.
Input kW
Input kW = Compressor + fan input power.
(3)
ESEER, refer to Performance Data, ESEER Calculationson page 19.
(4)
FSEER, refer to Performance Data, ESEER Calculationson page 19.
(5)
Free Cooling duties based on flow rate at conditions (1), 12°C return water temperature @ 5°C ambient and 20% Ethylene Glycol
Water Concentration.
(6)
Based on standard unit, for units fitted with options, please contact Airedale.
(7)
For minimum system volume, refer to Minimum System Water Volume Calculations, on page 14.
All performance data is supplied in accordance with BS EN 14511-1:2013