Disables/Enables the chiller remotely.
Compressor Anti Cycle
Control
Automatic via the Microprocessor.
Limits the condensing pressure by unloading above 35Barg.
Limits the evaporating pressure by unloading at the minimum pressure setpoint, which is
adjustable depending on system glycol content.
Disables/Enables the pump(s) remotely.
Remote Setback
Temperature Setpoint
Switch
A setback setpoint for supply water temperature can be selected to suit summer/winter
conditions or night setback.
Displays hours run of each compressor.
The control system integrity can be maintained by restricting access with a password
PIN number.
IMPORTANT: To change the PIN number; please contact Airedale at time of order
with the preferred 4 digit number.
Displays hours run of each pump.
Controlled units to be interfaced with most BMS, factory fitted,
please contact Airedale.
A wide range of protocols can be accommodated through the use of interface devices.
Available as a standard option are: ModBus/Jbus, Carel and Trend.
For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact Airedale.
Also available is Airedale’s own supervisory plug-in BMS card pCOWEB.
Based on Ethernet TCP/IP secure technology with SNMP features.
Requires no proprietary cabling or monitoring software and supplied pre programmed
with an IP address for ease of set up.
Allows remote alarm monitoring by sending alarm text messages to a nominated mobile
phone, factory set.