Technical Manual : 6521355 V1.8.0 07/2014
Performance Data
The quoted EER figures (General Specification, on page 29) cover the performance of the
unit ONLY at the standard rating conditions of 7/12°C water, 35°C ambient. The ESEER
calculation method has been developed by Eurovent to give a single value that is a
realistic indication of the efficiency of the chiller across the whole range of operation.
The ESEER value is calculated from the unit’s performance at 20, 25, 30 and 35°C
ambient temperatures for all loading stages, and with a fixed 7°C supply temperature. All
calculations assume the system operates with 100% water.
ESEER = A.EER
100%
+ B.EER
75%
+ C.EER
50%
+ D.EER
25%
A, B, C and D are weighting factors 0.03, 0.33, 0.41 and 0.25.
Percentage of Total Hours
FSEER CALCULATIONS
(Free Cooling)
Whilst the ESEER is useful for providing a true energy efficiency of a unit’s performance
over a year it does not offer any advantages for use of free-cooling which can significantly
reduce the unit’s lifecycle power consumption.
The FSEER calculation method has been developed by Airedale to give a single value
that is a realistic indication of the efficiency of the chiller across the whole range
of operation.
The quoted Airedale FSEER figures (General Specification, on page 29) are similar to the
ESEER and includes the unit’s free cooling capacity within the calculation. All calculations
for the FSEER use water with 20% ethylene glycol content. Flow rates are kept constant
for all conditions and are determined by the operation at 7/12°C, 35°C ambient.
Free cooling capacity is included within the units EER when available. DX cooling
capacity is included within the Chillers EER when the Free-cooling available is not
sufficient to satisfy the total cooling demand.
ESEER = A.EER
100%
+ B.EER
75%
+ C.EER
50%
+ D.EER
25%
A, B, C and D are weighting factors 0.05, 0.25, 0.47, 0.23.
Percentage of Total Hours
All performance data is supplied in accordance with BS EN 14511-1:2013